{"id":80809,"date":"2026-10-26T13:41:20","date_gmt":"2026-10-26T05:41:20","guid":{"rendered":"https:\/\/www.scondar.com\/?p=80809"},"modified":"2026-10-26T13:41:20","modified_gmt":"2026-10-26T05:41:20","slug":"network-rack-internal-harness-design-selecting-wire-to-board-connectors-for-power-distribution-in-active-networking-equipment","status":"publish","type":"post","link":"https:\/\/www.scondar.com\/ru\/2026\/10\/26\/network-rack-internal-harness-design-selecting-wire-to-board-connectors-for-power-distribution-in-active-networking-equipment\/","title":{"rendered":"Network Rack Internal Harness Design: Selecting Wire-to-Board Connectors for Power Distribution in Active Networking Equipment"},"content":{"rendered":"<h2>Application Context &amp; Design Challenge<\/h2>\n<p>In network rack environments, active equipment such as switches, routers, firewalls, and server nodes share a common engineering challenge: how to distribute power safely and reliably across densely populated PCBs in confined rack-mount form factors.<\/p>\n<p>Equipment designers and harness manufacturers typically face three compounding constraints simultaneously:<\/p>\n<p><strong>PCB Space Pressure: 1U and 2U rack units demand ultra-flat connector profiles, often pushing designers toward smaller pitch connectors even for power rails.<\/strong><\/p>\n<p>Current Density: Power rails in active networking equipment routinely carry 3A-9A per circuit, especially on 54V PoE (Power over Ethernet) bus rails and standby power domains.<\/p>\n<p><strong>Vibration &amp; Thermal Cycling: Data center racks can experience sustained vibration from cooling fans and thermal cycling from 24\/7 operation. Connector terminals must maintain contact integrity over thousands of thermal cycles.<\/strong><\/p>\n<p>Assembly Throughput: Internal harnesses inside network equipment are assembled in high volumes. Crimp-based wire-to-board connections offer consistent quality at scale, making connector selection a supply-chain decision as much as an engineering one.<\/p>\n<p>This article examines the connector parameters that matter most for network rack internal power harness design, and presents SCONDAR&#x27;s matching wire-to-board solutions for this application.<\/p>\n<h2>SCONDAR Product Matching for Network Rack Power Applications<\/h2>\n<p>For power distribution inside network rack equipment, the connector must bridge the gap between small pitch for PCB density and adequate current rating. SCONDAR&#x27;s SCT3001 series targets exactly this intersection.<\/p>\n<p>The SCT3001 is footprint-compatible with the Micro-Fit 3.0mm product line, a widely adopted industry standard in data center and networking hardware. It features isolated terminal geometry that provides dedicated ground paths, a meaningful advantage in noisy high-speed networking environments where EMI management is critical.<\/p>\n<p>For higher-power networking equipment such as core switches and router line cards, SCONDAR also offers the SCT3002, rated up to 9A with positive lock housing and fully isolated terminals. This series is a strong match for PCIe power domains and 54V PoE backbone rails in enterprise-grade network hardware.<\/p>\n<h2>Technical Specification Overview<\/h2>\n<p>The following table summarizes key electrical and mechanical specifications for SCONDAR&#x27;s primary network rack power connector recommendation.<\/p>\n<table>\n<thead>\n<tr>\n<th>Parameter<\/th>\n<th>SCONDAR SCT3001<\/th>\n<th>SCONDAR SCT3002<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>\u041a\u043e\u043d\u0442\u0430\u043a\u0442\u043d\u0430\u044f \u043f\u043b\u043e\u0449\u0430\u0434\u043a\u0430<\/td>\n<td>3,0 \u043c\u043c<\/td>\n<td>3,0 \u043c\u043c<\/td>\n<\/tr>\n<tr>\n<td>\u0422\u0435\u043a\u0443\u0449\u0438\u0439 \u0440\u0435\u0439\u0442\u0438\u043d\u0433<\/td>\n<td>5A<\/td>\n<td>9A<\/td>\n<\/tr>\n<tr>\n<td>\u041d\u043e\u043c\u0438\u043d\u0430\u043b\u044c\u043d\u043e\u0435 \u043d\u0430\u043f\u0440\u044f\u0436\u0435\u043d\u0438\u0435<\/td>\n<td>250V<\/td>\n<td>250V<\/td>\n<\/tr>\n<tr>\n<td>Temperature Range<\/td>\n<td>-40C to +105C<\/td>\n<td>-45C to +105C<\/td>\n<\/tr>\n<tr>\n<td>\u0421\u043e\u043f\u0440\u043e\u0442\u0438\u0432\u043b\u0435\u043d\u0438\u0435 \u043a\u043e\u043d\u0442\u0430\u043a\u0442\u043e\u0432<\/td>\n<td>10m Ohm Max<\/td>\n<td>10m Ohm Max<\/td>\n<\/tr>\n<tr>\n<td>No. of Positions<\/td>\n<td>1 to 12; Dual-row 2&#215;1 to 2&#215;12<\/td>\n<td>12+4 (PCIe config)<\/td>\n<\/tr>\n<tr>\n<td>\u0421\u0442\u0438\u043b\u044c \u0437\u0430\u0434\u0435\u043b\u043a\u0438<\/td>\n<td>Crimp \/ Male Tab<\/td>\n<td>Crimp \/ Male Tab<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h2>Design-In Considerations: Mechanical &amp; Process<\/h2>\n<h3>Wire Gauge Compatibility<\/h3>\n<p>The SCT3001 (5A rated) accepts AWG #20 to AWG #24 discrete wires. The SCT3002 (9A rated) accommodates AWG #16 to AWG #28, providing flexibility for power rails carrying different current loads on the same board. Designers should size wire gauges conservatively: for a 5A circuit, AWG #22 is recommended to minimize temperature rise within the rack thermal envelope.<\/p>\n<h3>Connector Locking Mechanism<\/h3>\n<p>Both the SCT3001 and SCT3002 feature friction lock housings as standard. For network equipment in high-vibration environments such as rack-mounted systems adjacent to cooling fans, the SCT3002 positive-lock latch variant provides additional retention force to prevent accidental disconnection during shipping, installation, or maintenance.<\/p>\n<h3>Crimp Quality Assurance<\/h3>\n<p>The SCT3001 and SCT3002 are crimp-style terminations. For harness assembly at scale, SCONDAR recommends the following quality checkpoints:<\/p>\n<ul>\n<li>Crimp Height: Measured post-press with a calibrated micrometer; tolerance typically within 0.05mm from the datasheet nominal. Off-height crimps indicate worn dies or incorrect terminal selection.<\/li>\n<li>Pull-Out Force: Tested per UL 486A-486B; SCONDAR&#x27;s production standard requires pull-out force to meet or exceed datasheet values across a minimum sample of 5 terminals per batch.<\/li>\n<li>Visual Inspection: Full-crimp condition: wire strands must be fully encased in the barrel with no visible gaps or extrusion. Partial crimps lead to intermittent opens under thermal cycling.<\/li>\n<li>Contact Resistance Verification: For power connectors, a contact resistance check maintains less than 10mOhm for the SCT3001\/3002, confirming the quality of the crimp-to-strand interface.<\/li>\n<\/ul>\n<h3>Board Layout and Polarization<\/h3>\n<p>The 3.0mm pitch of the SCT3001\/3002 series provides a balanced trade-off: sufficient pitch for reliable crimp termination on AWG #20-24 wires, while remaining compact enough for dual-row configurations in 1U rack equipment. The fully polarized housing prevents incorrect mating, a critical consideration during field service where technicians may handle pre-built internal harnesses under time pressure.<\/p>\n<h2>Quality Assurance and Supply Chain<\/h2>\n<p>SCONDAR operates an ISO 9001:2015-certified manufacturing facility in Dongguan, China, with an 80% automation rate and in-house quality testing capabilities including:<\/p>\n<ul>\n<li>Temperature and humidity chamber testing<\/li>\n<li>Salt spray testing for corrosion resistance<\/li>\n<li>Wire flex\/bend endurance testing<\/li>\n<li>Crimp cross-section analysis<\/li>\n<li>Insertion\/extraction force testing<\/li>\n<li>Hi-pot \/ dielectric withstanding voltage testing<\/li>\n<\/ul>\n<p>All SCONDAR wire-to-board connectors are UL-certified (E538921) and compliant with RoHS and REACH regulations. The company supports both bulk orders and small-batch fast-turnaround, with a sample kit service available for engineering validation before full production commitment.<\/p>\n<p>Supply chain-wise, SCONDAR maintains stock for popular configurations of the SCT3001 and SCT3002 series, supporting rapid deployment for both new product introduction and replacement demand from networking equipment manufacturers.<\/p>\n<h2>Frequently Asked Questions<\/h2>\n<h3>FAQ 1: How do I verify PCB footprint compatibility without re-layout?<\/h3>\n<p>Q: We are designing a replacement power connector for an existing switch board. How can we confirm SCONDAR&#x27;s SCT3001 is drop-in compatible without a full PCB re-layout?<\/p>\n<p>A: The SCT3001 is engineered as a footprint-compatible alternative to Micro-Fit. To verify compatibility:<\/p>\n<ol>\n<li>Cross-reference the SCONDAR datasheet header dimensions (pin spacing, row pitch, and mounting hole positions) against your existing board footprint. The 3.0mm contact pitch and dual-row layout match the industry standard.<\/li>\n<li>Confirm the tab width (male pin dimensions) matches your existing housing. SCONDAR&#x27;s SCT3001 male tab is standard Micro-Fit geometry.<\/li>\n<li>Download the CAD model (STEP file) from SCONDAR&#x27;s product page and perform a board clearance check in your ECAD tool to verify no mechanical interferences.<\/li>\n<\/ol>\n<p>Request a sample kit (available from SCONDAR) and run a physical fit-check before committing to production volumes.<\/p>\n<h3>FAQ 2: What long-term reliability can I expect in 24\/7 networking equipment?<\/h3>\n<p>Q: Our routers run continuously. What failure modes should we anticipate, and how does the SCT3001 perform under long-term thermal cycling?<\/p>\n<p>A: For 24\/7 networking equipment, the primary failure modes in wire-to-board power connectors are:<\/p>\n<ul>\n<li>Contact Resistance Creep: Over thousands of thermal cycles, the contact interface can oxidize or relax, increasing resistance. The SCT3001&#x27;s phosphor bronze contact material with tin plating maintains less than 10mOhm contact resistance under extended thermal aging.<\/li>\n<li>Terminal Withdrawal Force Degradation: If the housing lance loses tension, terminals can become loose. SCONDAR&#x27;s production standard includes insertion\/extraction force testing per batch.<\/li>\n<li>Vibration-Induced Disconnection: For rack environments with sustained fan vibration, the SCT3002&#x27;s positive lock variant is recommended for approximately 2-3x the retention force of a standard friction lock housing.<\/li>\n<li>Humidity and Corrosion: In uncontrolled rack environments, moisture ingress can be a concern. The SCT3001&#x27;s PA66 housing (UL94V-0 rated) provides good moisture resistance, and SCONDAR offers optional gold-plated contacts for enhanced corrosion resistance.<\/li>\n<\/ul>\n<p>Racks aren&#x27;t always climate-controlled, and the connectors that survive are the ones specified with the environment in mind\u2014housing material, plating, and lock design all earn their keep once humidity creeps in. If you&#x27;re deciding between SCT3001 and SCT3002 for a power or node harness and want to match the rating to your worst-case conditions, describe the environment in the comments. Prefer to validate first? Request samples for your own corrosion and thermal checks, or reach our support engineers with a spec. See the full range in the wire-to-board portfolio.<\/p>","protected":false},"excerpt":{"rendered":"<p>Application Context &amp; Design Challenge In network rack environments, active equipment such as switches, routers, firewalls, and server nodes share a common engineering challenge: how to distribute power safely and reliably across densely populated PCBs in confined rack-mount form factors. Equipment designers and harness manufacturers typically face three compounding constraints simultaneously: PCB Space Pressure: 1U [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":0,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[1],"tags":[],"class_list":["post-80809","post","type-post","status-publish","format-standard","hentry","category-uncategorized"],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v28.8 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>Network Rack Internal Harness Design: Selecting Wire-to-Board Connectors for Power Distribution in Active Networking Equipment - SCONDAR<\/title>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/www.scondar.com\/ru\/2026\/10\/26\/network-rack-internal-harness-design-selecting-wire-to-board-connectors-for-power-distribution-in-active-networking-equipment\/\" \/>\n<meta property=\"og:locale\" content=\"ru_RU\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"Network Rack Internal Harness Design: Selecting Wire-to-Board Connectors for Power Distribution in Active Networking Equipment - SCONDAR\" \/>\n<meta property=\"og:description\" content=\"Application Context &amp; Design Challenge In network rack environments, active equipment such as switches, routers, firewalls, and server nodes share a common engineering challenge: how to distribute power safely and reliably across densely populated PCBs in confined rack-mount form factors. Equipment designers and harness manufacturers typically face three compounding constraints simultaneously: PCB Space Pressure: 1U [&hellip;]\" \/>\n<meta property=\"og:url\" content=\"https:\/\/www.scondar.com\/ru\/2026\/10\/26\/network-rack-internal-harness-design-selecting-wire-to-board-connectors-for-power-distribution-in-active-networking-equipment\/\" \/>\n<meta property=\"og:site_name\" content=\"SCONDAR\" \/>\n<meta property=\"article:published_time\" content=\"2026-10-26T05:41:20+00:00\" \/>\n<meta name=\"author\" content=\"info@scondar.com\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:label1\" content=\"\u041d\u0430\u043f\u0438\u0441\u0430\u043d\u043e \u0430\u0432\u0442\u043e\u0440\u043e\u043c\" \/>\n\t<meta name=\"twitter:data1\" content=\"info@scondar.com\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/www.scondar.com\\\/2026\\\/10\\\/26\\\/network-rack-internal-harness-design-selecting-wire-to-board-connectors-for-power-distribution-in-active-networking-equipment\\\/#article\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.scondar.com\\\/2026\\\/10\\\/26\\\/network-rack-internal-harness-design-selecting-wire-to-board-connectors-for-power-distribution-in-active-networking-equipment\\\/\"},\"author\":{\"name\":\"info@scondar.com\",\"@id\":\"https:\\\/\\\/www.scondar.com\\\/#\\\/schema\\\/person\\\/5bdf51dcf11158ed6335d131d9eab9d3\"},\"headline\":\"Network Rack Internal Harness Design: Selecting Wire-to-Board Connectors for Power Distribution in Active Networking Equipment\",\"datePublished\":\"2026-10-26T05:41:20+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/www.scondar.com\\\/2026\\\/10\\\/26\\\/network-rack-internal-harness-design-selecting-wire-to-board-connectors-for-power-distribution-in-active-networking-equipment\\\/\"},\"wordCount\":1243,\"articleSection\":[\"Uncategorized\"],\"inLanguage\":\"ru-RU\"},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/www.scondar.com\\\/2026\\\/10\\\/26\\\/network-rack-internal-harness-design-selecting-wire-to-board-connectors-for-power-distribution-in-active-networking-equipment\\\/\",\"url\":\"https:\\\/\\\/www.scondar.com\\\/2026\\\/10\\\/26\\\/network-rack-internal-harness-design-selecting-wire-to-board-connectors-for-power-distribution-in-active-networking-equipment\\\/\",\"name\":\"Network Rack Internal Harness Design: Selecting Wire-to-Board Connectors for Power Distribution in Active Networking Equipment - SCONDAR\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.scondar.com\\\/#website\"},\"datePublished\":\"2026-10-26T05:41:20+00:00\",\"author\":{\"@id\":\"https:\\\/\\\/www.scondar.com\\\/#\\\/schema\\\/person\\\/5bdf51dcf11158ed6335d131d9eab9d3\"},\"breadcrumb\":{\"@id\":\"https:\\\/\\\/www.scondar.com\\\/2026\\\/10\\\/26\\\/network-rack-internal-harness-design-selecting-wire-to-board-connectors-for-power-distribution-in-active-networking-equipment\\\/#breadcrumb\"},\"inLanguage\":\"ru-RU\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\\\/\\\/www.scondar.com\\\/2026\\\/10\\\/26\\\/network-rack-internal-harness-design-selecting-wire-to-board-connectors-for-power-distribution-in-active-networking-equipment\\\/\"]}]},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/www.scondar.com\\\/2026\\\/10\\\/26\\\/network-rack-internal-harness-design-selecting-wire-to-board-connectors-for-power-distribution-in-active-networking-equipment\\\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\\\/\\\/www.scondar.com\\\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Network Rack Internal Harness Design: Selecting Wire-to-Board Connectors for Power Distribution in Active Networking Equipment\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/www.scondar.com\\\/#website\",\"url\":\"https:\\\/\\\/www.scondar.com\\\/\",\"name\":\"SCONDAR\",\"description\":\"\",\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\\\/\\\/www.scondar.com\\\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"ru-RU\"},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/www.scondar.com\\\/#\\\/schema\\\/person\\\/5bdf51dcf11158ed6335d131d9eab9d3\",\"name\":\"info@scondar.com\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"ru-RU\",\"@id\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/0d02c747c33c0b4784c58c9ca75c2de60c4223ffa72423b59f8872ce23079a38?s=96&d=mm&r=g\",\"url\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/0d02c747c33c0b4784c58c9ca75c2de60c4223ffa72423b59f8872ce23079a38?s=96&d=mm&r=g\",\"contentUrl\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/0d02c747c33c0b4784c58c9ca75c2de60c4223ffa72423b59f8872ce23079a38?s=96&d=mm&r=g\",\"caption\":\"info@scondar.com\"},\"sameAs\":[\"https:\\\/\\\/www.scondar.com\"],\"url\":\"https:\\\/\\\/www.scondar.com\\\/ru\\\/author\\\/scondar-2\\\/\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"Network Rack Internal Harness Design: Selecting Wire-to-Board Connectors for Power Distribution in Active Networking Equipment - SCONDAR","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/www.scondar.com\/ru\/2026\/10\/26\/network-rack-internal-harness-design-selecting-wire-to-board-connectors-for-power-distribution-in-active-networking-equipment\/","og_locale":"ru_RU","og_type":"article","og_title":"Network Rack Internal Harness Design: Selecting Wire-to-Board Connectors for Power Distribution in Active Networking Equipment - SCONDAR","og_description":"Application Context &amp; Design Challenge In network rack environments, active equipment such as switches, routers, firewalls, and server nodes share a common engineering challenge: how to distribute power safely and reliably across densely populated PCBs in confined rack-mount form factors. Equipment designers and harness manufacturers typically face three compounding constraints simultaneously: PCB Space Pressure: 1U [&hellip;]","og_url":"https:\/\/www.scondar.com\/ru\/2026\/10\/26\/network-rack-internal-harness-design-selecting-wire-to-board-connectors-for-power-distribution-in-active-networking-equipment\/","og_site_name":"SCONDAR","article_published_time":"2026-10-26T05:41:20+00:00","author":"info@scondar.com","twitter_card":"summary_large_image","twitter_misc":{"\u041d\u0430\u043f\u0438\u0441\u0430\u043d\u043e \u0430\u0432\u0442\u043e\u0440\u043e\u043c":"info@scondar.com"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/www.scondar.com\/2026\/10\/26\/network-rack-internal-harness-design-selecting-wire-to-board-connectors-for-power-distribution-in-active-networking-equipment\/#article","isPartOf":{"@id":"https:\/\/www.scondar.com\/2026\/10\/26\/network-rack-internal-harness-design-selecting-wire-to-board-connectors-for-power-distribution-in-active-networking-equipment\/"},"author":{"name":"info@scondar.com","@id":"https:\/\/www.scondar.com\/#\/schema\/person\/5bdf51dcf11158ed6335d131d9eab9d3"},"headline":"Network Rack Internal Harness Design: Selecting Wire-to-Board Connectors for Power Distribution in Active Networking Equipment","datePublished":"2026-10-26T05:41:20+00:00","mainEntityOfPage":{"@id":"https:\/\/www.scondar.com\/2026\/10\/26\/network-rack-internal-harness-design-selecting-wire-to-board-connectors-for-power-distribution-in-active-networking-equipment\/"},"wordCount":1243,"articleSection":["Uncategorized"],"inLanguage":"ru-RU"},{"@type":"WebPage","@id":"https:\/\/www.scondar.com\/2026\/10\/26\/network-rack-internal-harness-design-selecting-wire-to-board-connectors-for-power-distribution-in-active-networking-equipment\/","url":"https:\/\/www.scondar.com\/2026\/10\/26\/network-rack-internal-harness-design-selecting-wire-to-board-connectors-for-power-distribution-in-active-networking-equipment\/","name":"Network Rack Internal Harness Design: Selecting Wire-to-Board Connectors for Power Distribution in Active Networking Equipment - SCONDAR","isPartOf":{"@id":"https:\/\/www.scondar.com\/#website"},"datePublished":"2026-10-26T05:41:20+00:00","author":{"@id":"https:\/\/www.scondar.com\/#\/schema\/person\/5bdf51dcf11158ed6335d131d9eab9d3"},"breadcrumb":{"@id":"https:\/\/www.scondar.com\/2026\/10\/26\/network-rack-internal-harness-design-selecting-wire-to-board-connectors-for-power-distribution-in-active-networking-equipment\/#breadcrumb"},"inLanguage":"ru-RU","potentialAction":[{"@type":"ReadAction","target":["https:\/\/www.scondar.com\/2026\/10\/26\/network-rack-internal-harness-design-selecting-wire-to-board-connectors-for-power-distribution-in-active-networking-equipment\/"]}]},{"@type":"BreadcrumbList","@id":"https:\/\/www.scondar.com\/2026\/10\/26\/network-rack-internal-harness-design-selecting-wire-to-board-connectors-for-power-distribution-in-active-networking-equipment\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https:\/\/www.scondar.com\/"},{"@type":"ListItem","position":2,"name":"Network Rack Internal Harness Design: Selecting Wire-to-Board Connectors for Power Distribution in Active Networking Equipment"}]},{"@type":"WebSite","@id":"https:\/\/www.scondar.com\/#website","url":"https:\/\/www.scondar.com\/","name":"SCONDAR","description":"","potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/www.scondar.com\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"ru-RU"},{"@type":"Person","@id":"https:\/\/www.scondar.com\/#\/schema\/person\/5bdf51dcf11158ed6335d131d9eab9d3","name":"info@scondar.com","image":{"@type":"ImageObject","inLanguage":"ru-RU","@id":"https:\/\/secure.gravatar.com\/avatar\/0d02c747c33c0b4784c58c9ca75c2de60c4223ffa72423b59f8872ce23079a38?s=96&d=mm&r=g","url":"https:\/\/secure.gravatar.com\/avatar\/0d02c747c33c0b4784c58c9ca75c2de60c4223ffa72423b59f8872ce23079a38?s=96&d=mm&r=g","contentUrl":"https:\/\/secure.gravatar.com\/avatar\/0d02c747c33c0b4784c58c9ca75c2de60c4223ffa72423b59f8872ce23079a38?s=96&d=mm&r=g","caption":"info@scondar.com"},"sameAs":["https:\/\/www.scondar.com"],"url":"https:\/\/www.scondar.com\/ru\/author\/scondar-2\/"}]}},"_links":{"self":[{"href":"https:\/\/www.scondar.com\/ru\/wp-json\/wp\/v2\/posts\/80809","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.scondar.com\/ru\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.scondar.com\/ru\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.scondar.com\/ru\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/www.scondar.com\/ru\/wp-json\/wp\/v2\/comments?post=80809"}],"version-history":[{"count":1,"href":"https:\/\/www.scondar.com\/ru\/wp-json\/wp\/v2\/posts\/80809\/revisions"}],"predecessor-version":[{"id":80810,"href":"https:\/\/www.scondar.com\/ru\/wp-json\/wp\/v2\/posts\/80809\/revisions\/80810"}],"wp:attachment":[{"href":"https:\/\/www.scondar.com\/ru\/wp-json\/wp\/v2\/media?parent=80809"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.scondar.com\/ru\/wp-json\/wp\/v2\/categories?post=80809"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.scondar.com\/ru\/wp-json\/wp\/v2\/tags?post=80809"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}